Fireye MBCE-110FR-3 Flame Sensor Module, Single channel module, 110 VAC 50/60 Hz, use with flame rod, 3 sec. FFRT.
PRODUCT SPECIFICATIONS
Supply Voltage: MBCE-110FR - 110 VAC (+10%, -15%), 50/60 Hz
(@ 0.1 Amp consumption)
MBCE-230FR - 230 VAC (+10%, -15%), 50/60 Hz
(@ 0.1 Amp consumption)
Flame Relay Output: SPDT 2 Amp Resistive @ 110VAC, 1 Amp @ 30VDC
SPDT 1 Amp Resistive @ 230VAC, 1 Amp @ 30VDC
F
lame Fail Response Time: 1 or 3 seconds - depending on part number (-1, -3)
\Operating Temperature: - 40° F to 150° F (- 40° C to 65° C)
Storage Temperature: - 40° F to 176° F (- 40° C to 80° C)
Humidity: 85% RH (max), non-condensing.
Agency Approvals: (Note1
)
MBCE-110FR CE / EN298 / EN230
MBCE-230FR CE / EN298 / EN230
Shipping Weight: 1 lb (.5 Kg)
Flame Rod: S1 = Terminal 4
S2 = Terminal 8 (local panel ground)
Power: Terminals 4 and 8, - 240 - 360 VAC
Note: Measured with digital VOM
Terminals 5 and 8 are internally connected.
Sensitivity: Flame Rod - 3 µA @ 100 Meg ohms
IP-Rating IP-20
Test Jacks: Standby/No flame 4mA
Flame signal (Min) 6mA
Flame signal (Max) 20mA