Valve Body Assembly
Service Hot and chilled water models, up to 50% glycol. Steam models up to 15 psi (both
valve body and valve actuator must be rated for high temperature).
System Static Pressure Limits 300 psi (2068.4 kPa).
Close-off Refer to Table-2.
Fluid/Ambient Temperature Limits Refer to Table-1.
Seat Leakage ANSI class IV (0.01%) with pressure at inlet (B-port/A-port, if 3-way).
Body Forged brass.
Stem Nickel-plated.
Seat Brass.